Indication | PV (Character) | 4 digits, 7 segments Green 10 mm height |
SV (Setting Value) | 4 digits, 7 segments Red 8 mm height |
Various Function Indiacation | LED: Red (AL1, AL2, Out1, Out2 or RDY) |
Control Method | PID Auto-Tuning PID Self- Tuning | Proportional bank (P1) | 0.1 to 200.0% of setting limiter span |
Proportional band (P2) at Output 2 | 0.10 to 10.00 times (Times per P) |
Reset time (Integral) (I) | 1 to 3600 sec (0: Off) |
Rate time (Deviation) (D) | 1 to 3600 sec (0: Off) |
Cycle time (T1, T2) | 1 to 120 sec |
Dead band (D8) | -100.0 to +100.0 or -100 to +100C |
On/Off | Control sensitivity (C1,C2) | 0 to 999 or 0.0 to 999.9 C |
Off Point of Output 1 & 2 | Position of setting | -199 to 999 or 199.9 to 999.9 C |
Control Output | Relay Contact | 250V AC, 3A (Load resistance) 1 a contact (On heating/ cooling operation, output 2 is 250V AC, 2.4A load resistance, 1a contact |
SSR Drive Voltage | 0 to 12V DC (Load resistance: Max 600 or more) |
Sampling Time |
| 0.5 sec (Output change period is the same) |
Setting and Indication Accuracy | Thermocouple | +-(0.3% + 1 digit) of process value or +-2C, either of bigger numerial values is taken. (Ambient temperature: 23C +- 10C) 100 to 0C: +- 3C, 200 to 100CL +- 4C Thermocouple B under 400C is not regulated |
R.T.D. | +- (0.3% +- 1 digit) of process value or +- 0.9C, either of bigger numerical values is taken. (Ambient temperature: 23C +- 10C) Ambient temperature 23C +- (10C) Ambient temperature 0 to 50C: +- (0.5% +- digit) or 1.5C, either of bigger numerical values is taken |
Memory Element | EEPROM |
Voltage Source | 100V AC to 240V AC (50/60Hz) |
Weight | TTM-J4: less than 180g. TTM-J5: less than 240g |
Power Consumption | Less than 10VA (240V AC) |
Accessories | Instruction manual & installation attachment (TTM-J4) or installation meal instruments (TTM-J5) |
Operating Condition | 0 to 50C, 20 to 90%RH (under non- condensation) |
Storage Condition | -25 to 70C, 5 to 95% RH (under non- condensation) |
Functions | Manipurated Variable Limiter (ML1, MH1, ML2, MH2) | 0.0 to 100.0% |
Setting Limiter (SLL, SLH) | See Inpu and Range |
Selectable Control Mode (CNT) | Auto-Tuning PID type A-B, Normal- Reverse, Auto- Tuning PID- On/Off |
PV Correction Setting 0 point (PVS) | -199 to 999 or 199.9 to 999.9
|
PV Correction Setting Gain | 0.50 to 2.00 (times) |
Input Filter | 0 to 99 (sec) |
Manual Reset (PBB) | 0.0 to 100.0%, -100.0 to 100.0 (heating & cooling) of proportional band |
Timer Operation Mode (TMM) | 0.00 minute to 59.59 minutes, 0.00 hour to 99.59 hours: Accuracy: +- (1.5% +- 0.5sec) of setting time |
Decimal Point Shift (DP) | Decimal point display available (up to 999.9) |
Manual Control | Auto/Manual control can be switched by key |
Run/Ready | Run and Ready can be switched by key |
Blind Function | No indicaion available for non- required display |
Auto-Tuning (AT) Coefficient | After AT, the computed PV band is newly to set up with another coefficient |
FUNC key | Digit Shift Timer Start/Reset |
Priority Display | Arbitrary parameter screens are shifted to indication of operation mode by key (max: 9 screens) |
Lock Function (LOC) | 4 modes (Off, All, Operation Lock, Lock except Operaion Mode) |
Wach Dog Function | Data check by EEPROM (Err0), A/D converter check (Err1), and Auto-Tuning check (Err2), Built- in watch dog timer |
Event Output 1 (AL1) Event Output 2 (AL2 or OUT2) | Function: PV contact output (8 modes), Special contact output (3 modes), additional functions (3 modes) |
Setting Range: 199.9 to 999.9 or -1999 to 9999 C |
Sensitivity: 0.0 to 999.9 or 0 to 9999 C |
Rating: 250V AC 2.4A(Load resistance) 1a conact when selecting output 2at contact output 2, the output generates on cooling side during heaing/cooling. Contact polarity is selectable, either normal open or normal close |
Heating & Cooling | See Control Output in standard specification |